Features
00-10KP ac-20mA Hipot Tester, 0-10kVac @ 10mA / 0-15kVdc @ 5 mA
HT10000P AC: AC output to 10000 Volts. Delivers 1 through 8 milliamps. Custom outputs to 25 mA.
HT10000P DC: DC output to 14000 Volts. Delivers 1 through 5 milliamps.
Logic Controlled, One-button testing. LED indicators. Buzzer upon failure, test terminates. Test termination defeatable by switch on rear panel. Provided with arc detection circuit to properly detect hipot failures.
Rear panel adjustments; leakage limit, ramp time, test time and voltage.
Ergonomic design for safety and ease of use.
High voltage output jack.
Automatic voltage ramp-down circuit eliminates residual voltage.
Designed for product development and laboratory use.
High efficiency design, low power consumption.
All test leads included.
    
        
            | Voltage Range | 
            0-10000 VAC 0-14000 VDC | 
        
        
            | Current Range | 
            3 mA at 10 KVAC 1 mA at 14 KVDC | 
        
        
            | Input Voltage Requirements | 
            108-132 V, 50 /60 Hz, 2A max | 
        
        
            | Fuse Requirements | 
            120 VAC | 
        
        
            | Arc Detect | 
            Separate high Frequency circuit | 
        
        
            | Leakage Detect | 
            Separate Low frequency circuit | 
        
        
            | Ground Continuity | 
            N/A | 
        
        
            | Ground Continuity Current | 
            N/A | 
        
        
            | Test Time Range | 
            1 - 60 seconds | 
        
        
            | Ramp time Range | 
            1 - 5 Seconds | 
        
        
            | Voltage Meter Accuracy | 
            ± 2 % | 
        
        
            | Current Meter Accuracy | 
            ±0.1 mA | 
        
        
            | Resistance measure Range | 
            N/A | 
        
        
            | Resistance auto offset Range | 
            N/A | 
        
        
            | Resistance Measure Accuracy | 
            N/A | 
        
        
            | HV shutdown by Ground Fail | 
            N/A | 
        
        
            | Duty cycle | 
            100% | 
        
        
            | Discharge Time | 
            (Resistive Load) | 
        
        
            | Transformer Output | 
            < 500 VAC | 
        
        
            | Pass/Fail Repeatability | 
            ± 3 % | 
        
        
            | Output connector | 
            High Voltage Jack | 
        
        
            | Display | 
            4 digits LED display | 
        
        
            | Test indicator | 
            Led indicators | 
        
        
            | Failure Indicator | 
            Led indicators and buzzer | 
        
        
            | Programable | 
            No | 
        
        
            | PLC Interface | 
            No | 
        
        
            | TestLink | 
            N/A | 
        
        
            | Testminder | 
            No | 
        
        
            | Voltage Hold on failure | 
            Available | 
        
        
            | Top Mounted handle | 
            No | 
        
        
            | Test Defeat | 
            Ramp Time, Test Time and Breakdown Fail | 
        
        
            | Autoreset on Pass | 
            Optional | 
        
        
            | Operation Temperature | 
            15 - 40 °C | 
        
        
            | Relative Humidity Range | 
            0 - 90 % Non-condensing | 
        
        
            | Dimensions | 
            17" Wide x 5 High x 16.75 " Deep | 
        
        
            | Weight | 
            31 lB | 
        
        
            | Calibration | 
            One year calibration Certificate | 
        
        
            | Test Cords | 
            Return lead, High Voltage Test Lead, Power cord | 
        
        
            | HTS/Schedule B | 
            9030.39.0100 | 
        
        
            | ECCN | 
            3B992 |