Earth Continuity
Test Current |
+/- 200mA DC |
Display Range |
0.01 – 19.99Ω |
Pass Value |
User Defined |
Insulation Resistance
Test Voltage |
500V / 250VDC @ 1mA nominal |
Display Range |
0.01MΩ - 19.99MΩ |
Pass Value |
User Defined |
IEC Lead Test
Test Voltage |
5VAC nominal |
Test |
Live / Neutral Checks for o/c, s/c and crossed |
Protective Conductor Current/Load
Test Voltage |
Supply voltage, maximum load current 16A |
Display Ranges |
0.01mA to 19.99mA |
Pass Value |
User Defined |
Touch Current
Test Voltage |
Supply Voltage, maximum load current 16A |
Display Ranges |
0.00 – 3.50mA |
Pass Value |
User defined |
Load Power/Current
Test Voltage |
Supply Voltage, maximum load current 16A |
Test Duration |
Programmable up to a maximum of 255s depending on load. i.e. max duration is reduced for high loads. |
Display Range |
0.00kVA – 4.00kVA
0.00A – 16.00A |
Alternative Leakage Current
Test Voltage |
>25VAC <50VAC |
Display Range |
0.00mA to 19.99mA |
Pass Value |
User Defined |
RCD Test
Test Voltage |
230V +10%, -15% |
Test Current |
30mA / 150mA rms sinusoidal |
Display Range |
0ms - 2000ms (30mA), 0ms - 40ms (150mA) |
Test method |
Internal isolation to avoid tripping distribution board RCD |
Power Socket Test
Voltage Range |
207V – 253Vac |
Indicates configuration of voltage potential:- |
Line potential phase to earth
Line potential phase to neutral
Line potential neutral to earth |
General
Memory size |
2,000 Records |
Weight |
1.5kg |
Dimensions |
230mm x 150mm x 100mm |
Power Source |
Mains or rechargeable battery pack |
|