Earth continuity
Output Current |
200mA |
Test Voltage (o/c) |
9V DC nominal |
Test Duration (Class I Test) |
2s nominal |
Display Range |
0.01ohm to 19.99ohm |
Pass Value (Class I Test) |
0.2ohm |
Insulation resistance
Test Voltage |
250/500VDC @1mA nominal, < 2mA (s/c) |
Test Duration (Class I or II) |
2s |
Display Range |
0.01Mohm to 19.99Mohm |
Pass Value |
1.0MOhm Class I |
|
2.0MOhm Class II |
Equivalent leakage
Test Voltage |
40V Nominal AC 50Hz Open Circuit |
Test Duration |
2s nominal |
Display Range |
0.1mA to 19.99mA |
Pass Value |
0.75mA CLI / 0.25mA CL II |
IEC lead test
Test voltage |
5V DC nominal |
Test Duration |
Time for test (2s max) |
Test |
Live/Neutral Checks for o/c, s/c and crossed |
Protective Conductor Current
Test Voltage |
Supply Voltage, max current 13A |
Test Duration |
30s maximum |
Display Range |
0.15mA to 9.99mA |
Pass Value |
0.75mA/3.5mA (user selectable with 0.75mA as default) |
Touch current
Test Voltage |
Supply Voltage, max current 13A |
Test Duration |
30s maximum |
Display Range |
0.10mA to 5.00mA |
Pass Value |
0.25mA |
3 phase differential leakage current
*Requires 3 phase adaptor accessory |
|
Test Voltage |
3 phase supply voltage |
Test Duration |
continuous measurement |
Display Range |
0.10 mA to 9.99 mA |
Pass Value |
3.5mA |
RCD trip time
Test Voltage |
Mains supply voltage |
Test Current |
30mA |
Test Current Phase |
0°/180° auto switched on alternate tests |
Measuring Range |
0ms – 500ms |
Pass Value |
200ms |
Power socket check
Input voltage range |
225 – 254V AC max current 13A UK |
Measurement range |
50V to 250V |
|